List of Operating LCW Plant in Accelerator Area

Sl No

Location

Capacity of Plant

1

Indus – 1

600 KW

2

Indus – 2

4000 KW

3

IMA

300 KW

4

Magnet Testing Lab

200 KW

 

Specification for LCW Plant for Accelerator Machine

Plant

Indus – 1

Indus - 2 

Wattage

600 KW

4000 KW

Electrical Power

120 kVA

750 kVA

Primary Circuit

Flow Rate

60 m3/hr

240 m3/hr

Supply Pressure

10 kg/cm2

10 kg/cm2

Inlet Temperature

30 ° C ± 1 °C

30 ° C ± 1 °C

Electrical Conductivity

< 1 µs/cm

< 1 µs/cm

Surge Tank Volume

2 x 5.0 m3

2 x 7.5 m3

Secondary Circuit

Flow Rate

90 – 120 m3/hr

300 – 450 m3/hr

Supply Pressure

5 kg/cm2

5 kg/cm2

Hardness

< 2 ppm

< 2 ppm

DM Circuit

Flow Rate

0.5 m3/h (1m3/h max)

1 m3/h (3 m3/h max)

Charge between regenerations

20 m3

40 m3

I2lcwplant3D
This is the schematic view of the LCW Plant with the general layout of equipment

 

P0000480
LCW Plant Service block Area view with different sub system loops.

 

P0000488
LCW Plant Pumping System view with Instrumentations.

 

P0000487
LCW Plant Heat Exchanger view with control valves arrangement.

 

P0000483
LCW Plant Cooling Tower view located on the terrace with make up Tank.

 

P0000499
LCW Water Treatment Plant view.

 

Specification for RF Cavity Chiller Units for Accelerator Machine

Parameters

Indus-2

Microtron

Booster

Indus-1

Cooling Capacity

65 kW

400W

2500W

3500W

Pump Flow Rate

13 m3/h

5 LPM

25 LPM

80 LPM

Temperature Range

25 – 75 ºC

20 ~ 30 ºC

20 ~ 30 ºC

20 ~ 31 ºC

Temperature Stability

± 0.1 ºC

± 1 ºC

± 0.5 ºC

± 0.5 ºC

Maximum Design Temp.

85 ºC

50 ºC

50 ºC

50 ºC

Condenser

Split, Air Cooled

Air Cooled

Air Cooled

Split, Air Cooled

Evaporator

Brazed PHE

Dipped Tube

Dipped Tube

Brazed PHE

Heater Bank

32 kW, Insertion Type

NIL

NIL

2 KW

Control

Automatic, through PC

ON/OFF Ctrl

ON/OFF Ctrl

Automatic, through PC

 