List of Operating LCW Plant in Accelerator Area
Sl No |
Location |
Capacity of Plant |
1 |
Indus – 1 |
600 KW |
2 |
Indus – 2 |
4000 KW |
3 |
IMA |
300 KW |
4 |
Magnet Testing Lab |
200 KW |
Specification for LCW Plant for Accelerator Machine |
Plant |
Indus – 1 |
Indus - 2 |
Wattage |
600 KW |
4000 KW |
Electrical Power |
120 kVA |
750 kVA |
| Primary Circuit |
Flow Rate |
60 m3/hr |
240 m3/hr |
Supply Pressure |
10 kg/cm2 |
10 kg/cm2 |
Inlet Temperature |
30 ° C ± 1 °C |
30 ° C ± 1 °C |
Electrical Conductivity |
< 1 µs/cm |
< 1 µs/cm |
Surge Tank Volume |
2 x 5.0 m3 |
2 x 7.5 m3 |
Secondary Circuit |
Flow Rate |
90 – 120 m3/hr |
300 – 450 m3/hr |
Supply Pressure |
5 kg/cm2 |
5 kg/cm2 |
Hardness |
< 2 ppm |
< 2 ppm |
DM Circuit |
Flow Rate |
0.5 m3/h (1m3/h max) |
1 m3/h (3 m3/h max) |
Charge between regenerations |
20 m3 |
40 m3 |
|
This is the schematic view of the LCW Plant with the general layout of equipment |
|
LCW Plant Service block Area view with different sub system loops. |
|
LCW Plant Pumping System view with Instrumentations. |
|
LCW Plant Heat Exchanger view with control valves arrangement. |
|
LCW Plant Cooling Tower view located on the terrace with make up Tank. |
|
LCW Water Treatment Plant view. |
Specification for RF Cavity Chiller Units for Accelerator Machine |
Parameters |
Indus-2 |
Microtron |
Booster |
Indus-1 |
Cooling Capacity |
65 kW |
400W |
2500W |
3500W |
Pump Flow Rate |
13 m3/h |
5 LPM |
25 LPM |
80 LPM |
Temperature Range |
25 – 75 ºC |
20 ~ 30 ºC |
20 ~ 30 ºC |
20 ~ 31 ºC |
Temperature Stability |
± 0.1 ºC |
± 1 ºC |
± 0.5 ºC |
± 0.5 ºC |
Maximum Design Temp. |
85 ºC |
50 ºC |
50 ºC |
50 ºC |
Condenser |
Split, Air Cooled |
Air Cooled |
Air Cooled |
Split, Air Cooled |
Evaporator |
Brazed PHE |
Dipped Tube |
Dipped Tube |
Brazed PHE |
Heater Bank |
32 kW, Insertion Type |
NIL |
NIL |
2 KW |
Control |
Automatic, through PC |
ON/OFF Ctrl |
ON/OFF Ctrl |
Automatic, through PC |
|